Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T08CM02020
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/10/2012 | ELECTRIC - INTERMEDIATE | Approved | ||
| 08/03/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | OK TO MAIN LUGS OF ALL PANELS OK TRANSFORMERS (3) 1) BLOW OUT ECESS DIRT AND FOREIGN MATERIAL 2) STRAP GROUND FOR XFMRS 3) CLEAN SURFACE UNDER GROUND LUG AND ADD BOLT 4) WILL NEED NEW FGI TEST 2 30.95 OK TO PWR CL E N. THRU D E. |
|
| 08/01/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 07/23/2012 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 07/19/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 06/24/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) ANSWERED QUESTIONS |
|
| 06/18/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALLS ROOMS #122, 139 & 138 |
|
| 06/14/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS ROOMS 101, 103, 102 & WEST ARCH WALL 109 WEST OF DOOR 151, 152 |
|
| 06/10/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) PROTECT CONDUITS AT BASE PLATE 2) PROTECT M/C CABLES LESS THAN 1 1/4" AT STUDS 3) STRAP TO BE WITHIN 12" OF BOXES 4) OK ROOMS 110,120,121,113,111,112,144,147,118 AND 119 AFTER CORRECTIONS |
|
| 06/08/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) USE APPROVED STRAPS FOR M/C CABLES 2) DO NOT BUNDLE M/C CABLES 3) MISSING "P" RUNS 4) OK EXTERIOR WALLS AREAS 3 & 4 |
|
| 06/02/2010 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 04/22/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* DJ WALL OK TO ONE SIDE SALES OUTER WALL OK BATHROOM SALES WALL OK TO ONE SIDE |
|
| 02/09/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* DISCUSSED SES LOCATION WITH CONTR. |
|
| 11/12/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* ADD TEMP CONST. POWER TO PERMIT |