Permit: T08CM02020

Parcel: 11901051L


Addresses:

295 W 40TH ST


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T08CM02020

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
09/10/2012 ELECTRIC - INTERMEDIATE Approved
08/03/2012 ELECTRIC - INTERMEDIATE Partial Approval OK TO MAIN LUGS OF ALL PANELS OK TRANSFORMERS (3)
1) BLOW OUT ECESS DIRT AND FOREIGN MATERIAL
2) STRAP GROUND FOR XFMRS
3) CLEAN SURFACE UNDER GROUND LUG AND ADD BOLT
4) WILL NEED NEW FGI TEST 2 30.95
OK TO PWR CL E N. THRU D E.
08/01/2012 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
07/23/2012 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
07/19/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
06/24/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) ANSWERED QUESTIONS
06/18/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK WALLS ROOMS #122, 139 & 138
06/14/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS ROOMS 101, 103, 102 & WEST ARCH WALL 109 WEST OF DOOR 151, 152
06/10/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) PROTECT CONDUITS AT BASE PLATE
2) PROTECT M/C CABLES LESS THAN 1 1/4" AT STUDS
3) STRAP TO BE WITHIN 12" OF BOXES
4) OK ROOMS 110,120,121,113,111,112,144,147,118 AND 119 AFTER CORRECTIONS
06/08/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) USE APPROVED STRAPS FOR M/C CABLES
2) DO NOT BUNDLE M/C CABLES
3) MISSING "P" RUNS
4) OK EXTERIOR WALLS AREAS 3 & 4
06/02/2010 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
04/22/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
DJ WALL OK TO ONE SIDE
SALES OUTER WALL OK
BATHROOM SALES WALL OK TO ONE SIDE
02/09/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
DISCUSSED SES LOCATION WITH CONTR.
11/12/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
ADD TEMP CONST. POWER TO PERMIT