Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/10/2012 | BUILDING ABOVE CEILING | Approved | ||
| 08/07/2012 | BUILDING ABOVE CEILING | Partial Approval | 1) SHEETROCK ON SERVICE AREA OFFICE WALL BOTH SIDES OK 2) 01036 AND 02036 OK AT RESTROOM ENTRY 3) PLUMBING IN RESTROOM WALLS OK |
|
| 08/03/2012 | BUILDING ABOVE CEILING | Partial Approval | OK TO MAIN LUGS OF ALL PANELS OK TRANSFORMERS (3) 1) BLOW OUT ECESS DIRT AND FOREIGN MATERIAL 2) STRAP GROUND FOR XFMRS 3) CLEAN SURFACE UNDER GROUND LUG AND ADD BOLT 4) WILL NEED NEW FGI TEST 2 30.95 T-BAR BACK OF HOUSE OK |
|
| 08/01/2012 | BUILDING ABOVE CEILING | Partial Approval | 1) CANNOT USE DRYWALL SCREWS "L" EDGE RUNNERS NO EVIDENCE OF LEAKAGE AT ROOF DRAINS-BOTTOM |