Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/31/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1. A DISCONNECTING MEANS IS NEEDED FOR WATER HEATER 2. USE TERMINAL ENDS WITH STRANDED CONDUCTORS 3. LABEL PANEL DIRECTORY AS PER 408.4 NO ABBREVIATIONS OK FINAL AFTER CORRECTIONS |
|
| 10/28/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. COMPLETE LTG. WEST ROOM 2. MUST HAVE 36" WORKING CLEARANCE IN FRONT OF BREAKER PANEL. REMOVE COVER FOR INSPECTION. 3. STRAP GROUND WIRE TO WALL OF BLD. 4. INSTALL UPDATED DIRECTORY AT MAIN PANEL |