2272 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/31/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
1. A DISCONNECTING MEANS IS NEEDED FOR WATER HEATER
2. USE TERMINAL ENDS WITH STRANDED CONDUCTORS
3. LABEL PANEL DIRECTORY AS PER 408.4 NO ABBREVIATIONS

OK FINAL AFTER CORRECTIONS
10/28/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. COMPLETE LTG. WEST ROOM
2. MUST HAVE 36" WORKING CLEARANCE IN FRONT OF BREAKER PANEL. REMOVE COVER FOR INSPECTION.
3. STRAP GROUND WIRE TO WALL OF BLD.
4. INSTALL UPDATED DIRECTORY AT MAIN PANEL