Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/04/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/28/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. NEED A 2ND GROUND ROD 2. GROUNDING ELECTRODE TO BE BONDED PER 250.64 3. FINISH #3 PREVIOUS INSPECTION |
|
| 07/18/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SEAL OPEN KNOCKOUTS IN SUB-PANEL 2. INSTALL GROUNDING ELECTRODE SYSTEM FOR SUB-PANEL 3. EQUIPMENT GROUNDS TO TERMINATE ON GROUND BAR IN SUB-PANEL 4. HAVE SECTIONS OF EMT THAT ARE NOT GROUNDED BECAUSE HAVE NON-METALLIC RACEWAYS @ EACH END INSTALL METALLIC RACEWAYS TO PROPERLY GROUND EMT |
|
| 07/17/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* NO ACCESS. LOCKED UP. INSPECTION TIMES START @ 7:30 AM |