Permit: T08CM01923

Parcel: 10510010D

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T08CM01923

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
09/12/2008 ELECTRIC - ABOVE CEILING Approved
09/09/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK FROM LOBBY EAST
09/05/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK 103 THRU 118
OPEN AREA 125, 119, 123-120
09/02/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. SUPPORT WIRES TO BE PER 300.11 AND 330.17
2. SUPPORT CONDUIT
3. SECURE CABLES UPON EXIT OF CABLE TRAY

OK BORDERS EXCEPT AS NOTED
07/24/2008 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
ANSWER DERATING QUESTIONS