Permit: T08CM01845

Parcel: 138144510

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T08CM01845

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/02/2009 MECHANICAL - FINAL Approved IVRS - Inspection :*
04/01/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. ALL ITEMS DATED 3/26/09 COMPLETE
2. PROVIDE LATERAL BRACING AT 8207 GUARD RAIL
3. PROVIDE SERVICE RECEPT. ON ROOF
03/26/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. 8103 CONDENSATE NOT PROPERLY TERMINATED, PRIMER NOT USED, NO SECONDARY DRAIN. COMBUSTIBLE MATERIAL TOO CLOSE TO FLUE PIPING (EASY TRAP)
2. 8104 NO PRIMER ON PVC PIPING, PVC EXPOSED TO EXTERIOR MUST BE PAINTED WITH LATEX PAINT, NO SECONDARY DRAIN RE-ROUTE REF. LINES
3. 8207 PROVIDE GUARD RAIL AT RTU CONDENSOR RE-ROUTE REF. PIPING OUT OF WAY OF WATER HEATER
4. 8208 PROVIDE GUARD RAIL AT RTU CONDENSOR
5. PROVIDE ACCESS TO ROOF