Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T08CM01845
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/01/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
03/13/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) CALL FOR FINAL AFTER POWER CHECK |
|
12/08/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK ROUGH WIRING 2. UNGROUNDED GROUNDING TYPE RECEPTACLES CANNOT BE USED ON UNGROUNDED SYSTEM - NOT IN SCOPE OF WORK PER THIS PERMIT BUT NEEDS TO BE ADDRESSED 3. SERVICE EQUIP. IN NEED OF UPGRADE WATER DAMAGE, NOT RATED FOR OUTDOOR USE |
|
12/02/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. STRAP NM CABLE WITHIN 8" OF SINGLE GANG AND 12" OF OTHER BOXES 2. TIGHTEN LOOSE CONNECTORS AT SUB-PANELS 3. PROPERLY GROUND ALL METAL JUNCTION BOXES 4. SECURE NM CABLE TO EXHAUST FANS 5. USE APPROVED MEANS TO PROTECT NM CABLE FROM SHARP METAL EDGES 6. FINISH PREVIOUS INSPECTIONS #1, 2 AND 4 |
|
08/08/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. PROVIDE LISTING INFO FOR CONNECTORS AND COUPS TO BE APPROVED CONCRETE TITE 2. MC CABLE NOTCHED IN MASONRY WALLS TO BE MIN. 1 1/4 INCHES FROM FINISHED WALL PER 300.4 NEC 3. PLANS/PERMIT? 4. ALSO, NOTE THAT SERVICE EQUIP. IS OUT-DATED NOT RATED FOR OUTDOOR USE. |