Permit: T08CM01845

Parcel: 138144510

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T08CM01845

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
04/01/2009 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
03/13/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) CALL FOR FINAL AFTER POWER CHECK
12/08/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK ROUGH WIRING
2. UNGROUNDED GROUNDING TYPE RECEPTACLES CANNOT BE USED ON UNGROUNDED SYSTEM - NOT IN SCOPE OF WORK PER THIS PERMIT BUT NEEDS TO BE ADDRESSED
3. SERVICE EQUIP. IN NEED OF UPGRADE
WATER DAMAGE, NOT RATED FOR OUTDOOR USE
12/02/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. STRAP NM CABLE WITHIN 8" OF SINGLE GANG AND 12" OF OTHER BOXES
2. TIGHTEN LOOSE CONNECTORS AT SUB-PANELS
3. PROPERLY GROUND ALL METAL JUNCTION BOXES
4. SECURE NM CABLE TO EXHAUST FANS
5. USE APPROVED MEANS TO PROTECT NM CABLE FROM SHARP METAL EDGES
6. FINISH PREVIOUS INSPECTIONS #1, 2 AND 4
08/08/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. PROVIDE LISTING INFO FOR CONNECTORS AND COUPS TO BE APPROVED CONCRETE TITE
2. MC CABLE NOTCHED IN MASONRY WALLS TO BE MIN. 1 1/4 INCHES FROM FINISHED WALL PER 300.4 NEC
3. PLANS/PERMIT?
4. ALSO, NOTE THAT SERVICE EQUIP. IS OUT-DATED
NOT RATED FOR OUTDOOR USE.