Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/15/2008 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* OK FOR CEILING TILES WILL CHECK FAN COIL DISCONNECT ON FINAL MAINTAIN CLEARANCE IN FRONT OF FAN COIL |
|
| 08/12/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* PROVIDE DRAIN PAN SUPPORT REFER LINE FINISH INSULATING |
|
| 08/08/2008 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SECONDARY DRAIN PAN DOES NOT FIT UNDER FAN COIL 2. PAN MUST BE MIN. 1 1/2" LARGER ON ALL SIDES OF FAN COIL 3. PLANS REQUIRE COPPER CONDENSATE DRAIN 4. SUPPORT WITH STEEL CLEVIS HANGERS AS PER PLAN 5. INSTALL ALL FLEX DUCTS PER DETAILS ON PLANS 6. USE LISTED TAPE ON ALL FLEX DUCT CONNECTIONS 7. ALL DUCT WRAP MUST BE MIN. 1 1/2" WITH VAPOR BARRIER 8. SUPPORT REFRIGERATION LINES 9. SUPPORT FLEX DUCTS EVERY 5' |