Permit: T08CM01844

Parcel: 133146610

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
08/15/2008 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
OK FOR CEILING TILES
WILL CHECK FAN COIL DISCONNECT ON FINAL
MAINTAIN CLEARANCE IN FRONT OF FAN COIL
08/12/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
PROVIDE DRAIN PAN
SUPPORT REFER LINE
FINISH INSULATING
08/08/2008 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SECONDARY DRAIN PAN DOES NOT FIT UNDER FAN COIL
2. PAN MUST BE MIN. 1 1/2" LARGER ON ALL SIDES OF
FAN COIL
3. PLANS REQUIRE COPPER CONDENSATE DRAIN
4. SUPPORT WITH STEEL CLEVIS HANGERS AS PER PLAN
5. INSTALL ALL FLEX DUCTS PER DETAILS ON PLANS
6. USE LISTED TAPE ON ALL FLEX DUCT CONNECTIONS
7. ALL DUCT WRAP MUST BE MIN. 1 1/2" WITH VAPOR BARRIER
8. SUPPORT REFRIGERATION LINES
9. SUPPORT FLEX DUCTS EVERY 5'