Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/29/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/28/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROPERLY STRAP SUPPORT MC CABLE ABOVE CEILING 2. HAVE OPEN JUNCTION BOX ABOVE CEILING 3. EXCEEDING BENDING RADIUS ON MC CABLE ABOVE CEILING 4. HAVE RECEPTACLE WITH NO POWER 5. NEED TO HAVE APPROVED ELECTRIC PLANS ON SITE 6. INSTALL TIE WIRES ON EXIT SIGNS TO BUILDING STRUCTURE 7. NEED DETAILED PANEL DIRECTORY 8. NEED TO BE ABLE TO TURN OFF LIGHTING FOR TESTING OF EM/EXITS 9. NEED ACCESS TO ROOF 10. WHERE IS EXHAUST FAN TIME CLOCK? 11. HAVE ELECTRICAL CONTRACTOR GO THROUGH ENTIRE JOB INSTALL PER PLAN & NEC |
|
| 08/27/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELED BY CONTRACTOR |