Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/27/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/22/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* FINISH #1 & #7 VERIFY BONDING FROM MANUFACTURE OF SIGNS |
|
| 10/21/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK ROOF 1. BOND SECTIONS OF SIGNS PER 600.7 2. BOXES MORE THAN 1/4" FROM BOXES TO SURFACE 314.20 3. TIGHTEN LOOSE FITTING AT WATER HEATER 4. USE TERMINAL END WITH STRANDED CONDUCTORS UNDER SCREWS 5. PANEL DIRECTORY TO BE AS PER 408.4 - NO ABBREVIATIONS AND DISTINGUISHABLE FROM ONE ANOTHER 6. PROPERLY GROUND FRONT SHOWROOM LIGHTS NO SHEETMETAL THREAD SCREWS 7. SUPPORT M/C CABLE AS PER CODE FOR FLOOR BOXES |