Permit: T08CM01818

Parcel: 10511061R

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/27/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/22/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
FINISH #1 & #7
VERIFY BONDING FROM MANUFACTURE OF SIGNS
10/21/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK ROOF

1. BOND SECTIONS OF SIGNS PER 600.7
2. BOXES MORE THAN 1/4" FROM BOXES TO SURFACE 314.20
3. TIGHTEN LOOSE FITTING AT WATER HEATER
4. USE TERMINAL END WITH STRANDED CONDUCTORS UNDER SCREWS
5. PANEL DIRECTORY TO BE AS PER 408.4 - NO ABBREVIATIONS AND DISTINGUISHABLE FROM ONE ANOTHER
6. PROPERLY GROUND FRONT SHOWROOM LIGHTS
NO SHEETMETAL THREAD SCREWS
7. SUPPORT M/C CABLE AS PER CODE FOR FLOOR BOXES