Permit: T08CM01812

Parcel: 12201001B

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/08/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/30/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
EM LIGHTING NOT PER PLAN
WIRE PER PLAN/MISSING REMOTE HEAD @ FRONT ENTRY
07/08/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. COMPLETE ITEM #4, #5 FROM INSPECTION ON 6/30/08
2. REVISE PLANS AND PANEL SCHEDULES
06/30/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. FINISH PONY WALL AT RECEPTION
2. CLEAN PAINT & FOREIGN MATERIAL FROM DEVICE TERMINATIONS
3. FINISH DEVICES AND PLATES
4. FRONT EXIT/FLOODS TO BE ON CIRCUIT SERVED 700.12
5. PLEASE REVISE PLANS FOR LIGHTING & LOADS (IECC)
6. BOXES MORE THAN 1/4" FROM BOXES TO SURFACE
7. MISSING EM FLOODS