Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/05/2008 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* OK FOR CEILING TILES MECHANICAL ONLY |
|
| 09/02/2008 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE BRANCH TAPS PER DETAIL 7 SHEET M2.01 (REFEE ASSESSED IF NOT DONE ON NEXT INSPECTION) 2. SEAL ALL VAPOR BARRIERS (NO INSULATION SHOWING) |
|
| 08/15/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. PROVIDE BRANCH TAPS PER DETAIL 7 SHEET M2.01 2. COMPLETE DUCT INSTALLATION 3. PROVIDE 45 DEG. TAPS INTO EXHAUST RISER FOR RESTROOM FANS |