Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/08/2008 | FRAMING | Approved | IVRS - Inspection :* | |
| 08/07/2008 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED TO REPLACE OVER KNOTCHED STUDS ON EAST BEARING WALL OR USE A STUD SHOE, CANNOT BE OVER 40 PERCENT (4 STUDS) 2) WILL NEED PROTECTION PLATES ON ALL ELECTRICAL WIRNG LESS THAN 1 1/4" FROM EDGE OF 2 X 4 3) NEED TO FIRESEAL ALL PENETRATIONS IN TOP PLATE THAT ARE NOT BEING USED 4) OPENING AT GARAGE DOOR-REQUIRES 2 KING STUDS AND 2 JACK STUDS, NEED TO BE ABLE TO VERIFY (1 SEE ONLY 1 JACK STUD) |