Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM01754
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/11/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
06/10/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SPLICES IN UNDERGROUND JUNCTION TO BOX TO BE LISTED FOR WET LOCATION 2. WHEN PHASE CONDUCTORS UPSIZED EQUIPMENT GROUND TO BE INCREASED IN SIZE ALSO 3. NEED TO HAVE EQUIPMENT OPEN FOR INSPECTION PANEL BOARD LOCATION |