Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/11/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/10/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SPLICES IN UNDERGROUND JUNCTION TO BOX TO BE LISTED FOR WET LOCATION 2. WHEN PHASE CONDUCTORS UPSIZED EQUIPMENT GROUND TO BE INCREASED IN SIZE ALSO 3. NEED TO HAVE EQUIPMENT OPEN FOR INSPECTION PANEL BOARD LOCATION |