Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/26/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/12/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK EM LIGHTS |
|
| 11/07/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. EM LIGHTS SALES FLOOR NOT WORKING 2. CHECK FINAL TIE TO POWER |
|
| 11/06/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* FINISH INSPECTING NEXT TIME 1. PANEL DIRECTORY TO BE AS PER 408.4 - NO ABBREVIATIONS 2. SHEETMETAL THREAD SCREWS NOT ALLOWED FOR GROUNDING 250.8 AND CLEAN SURFACE UNDER LUG 250.12 3. LABEL DISCONNECT AND PANEL 4. SECURE TRANSFORMER TO STRUCTURE 5. STRAP CONDUIT ABOVE CONTACTOR 6. EM & EXIT LIGHTS NOT WORKING |