Permit: T08CM01722

Parcel: 12212011A

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
08/27/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
OK FOR FINAL
AIR BALANCE OK
08/26/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
REMOVE TRAPS FROM NEW AC UNITS.
SEE NOTE ON AC UNIT.
MARK DATA PLATES ON ALL UNITS AND FUSE ACCORDINGLY
VENTS ON EXISTING TRAPS MUST BE DOWNSTREAM OF TRAP
RELOCATE ELEC. DISCONNECTS BLOCKING ACCESS TO SERVICE PANELS A/C 12 & A/C 3 & A/C 8
PROVIDE AIR BALANCE REPORT