Permit: T08CM01722

Parcel: 12212011A

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
08/13/2008 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
OK FOR CEILING TILES
08/12/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK CEILING TILES NORTH HALF OF BLDG.
07/18/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
07/17/2008 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. VERIFY ALL DUCT JOINTS SEALED PER SPECS
2. PROVIDE BRANCH TAKE OFF PER DETAIL 104