Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T08CM01693
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/21/2009 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
04/02/2009 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED BY OWNER |
|
03/27/2009 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* 1) ITEM #5 NOT MET 2) BEDROOM #2 NORTH WALL RECEPTACLE HAS AN OPEN GROUND |
|
03/24/2009 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) KITCHEN COUNTER SPACE REQUIRES 2 GFI PROTECTED CIRCUITS 2) NOT ALL BEDROOM RECEPTACLES ON ARC-FAULT INTERRUPTERS 3) MECHANICAL NOT COMPLETED 4) MISSING ANTI-TIP FOR RANGE 5) WILL NEED TO FLIP 1/2 HOT FOR GARBAGE DISPOSAL 6) NEED TO FIRE SEAL MECHANICAL BEHIND KITCHEN 7) NEED TO INSTALL PROPER CAPS ON CLEANOUTS |