Permit: T08CM01688

Parcel: 12218274A


Addresses:

1160 N WINSTEL BL

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
04/22/2009 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
03/31/2009 MECHANICAL - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
03/30/2009 MECHANICAL - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
03/25/2009 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
03/24/2009 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
03/23/2009 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
03/04/2009 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
03/03/2009 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
03/02/2009 MECHANICAL - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
02/19/2009 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. REMOVE ALL COMBUSTIBLE MATERIAL FROM PLENUM
2. REVISE PLANS TO REFLECT CHANGES BEING MADE
3. E2 TRAPS RATED FOR PLENUM CEILINGS PER MANUF.
02/17/2009 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
TRANSFER DUCTS NOT PER PLANS
EXHAUST DUCTS NOT PER PLANS
10/15/2008 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. PROVIDE DUCT SMOKE DETECTORS AT EACH FAN COIL.
2. REMOVE ALL COMBUSTIBLES FROM PLENUM CEILING.
3. OK TO SHEETROCK HARD LIDS.