Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM01683
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/13/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
08/12/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. USE ALL HARDWARE TO MOUNT RECEPTACLES IN INDUSTRIAL COVERS 2. NEED TO GROUND GROUND BAR IN COMPUTER ROOM 3. PROPERLY CONNECT GROUND BAR TO PANEL CANNOT USE TECH SCREWS 4. INSTALL ARCH FLASH WARNING ON PANEL 5. CONDUCTORS TO CONDENSATE PUMP TO BE INSTALLED IN APPROVED RACEWAY 6. SEAL OPEN KNOCKNOUT IN CONDENSING UNIT 7. CIRCUITS TO FURNITURE TO HAVE APPROVED HANDLE TIES OR MULTIPLE BREAKERS 8. PROVIDE INFORMATION ON AC UNIT 9. HAVE SOMEONE ON SITE TO TEST EM LIGHTS 10. FINISH INSTALLING WORK STATIONS |