Permit: T08CM01683

Parcel: 12615011C

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM01683

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/13/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/12/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. USE ALL HARDWARE TO MOUNT RECEPTACLES IN INDUSTRIAL COVERS
2. NEED TO GROUND GROUND BAR IN COMPUTER ROOM
3. PROPERLY CONNECT GROUND BAR TO PANEL CANNOT USE TECH SCREWS
4. INSTALL ARCH FLASH WARNING ON PANEL
5. CONDUCTORS TO CONDENSATE PUMP TO BE INSTALLED IN APPROVED RACEWAY
6. SEAL OPEN KNOCKNOUT IN CONDENSING UNIT
7. CIRCUITS TO FURNITURE TO HAVE APPROVED HANDLE TIES OR MULTIPLE BREAKERS
8. PROVIDE INFORMATION ON AC UNIT
9. HAVE SOMEONE ON SITE TO TEST EM LIGHTS
10. FINISH INSTALLING WORK STATIONS