Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Permit Number - T08CM01675

Inspection Description - ELECTRIC - RECONNECT

Inspection Status - Approved

Date Description Inspector Results Comments
07/25/2008 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
07/22/2008 ELECTRIC - RECONNECT Partial Approval IVRS - Inspection :*
07/17/2008 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL GROUNDING ELECTRODE SYSTEM
2. NEED MIN. 10' CLEARANCE FROM GRADE TO OVERHEAD CONDUCTORS
3. SERVICE EQUIPMENT @ BUILDING TO BE UNLOCKED FOR INSPECTION
4. ARE THERE ELECTRIC PLANS? SHEET #2
REFERENCES E1 & E2
5. CONDUCTORS TO BE LISTED AND MARKED SUNLIGHT RESISTANT
6. CONDUCTOR SIZE TO BE #1 FOR 125 AMP. BREAKER
7. RECALL WHEN READY