Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
Permit Number - T08CM01675
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/25/2008 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
07/22/2008 | ELECTRIC - RECONNECT | Partial Approval | IVRS - Inspection :* | |
07/17/2008 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL GROUNDING ELECTRODE SYSTEM 2. NEED MIN. 10' CLEARANCE FROM GRADE TO OVERHEAD CONDUCTORS 3. SERVICE EQUIPMENT @ BUILDING TO BE UNLOCKED FOR INSPECTION 4. ARE THERE ELECTRIC PLANS? SHEET #2 REFERENCES E1 & E2 5. CONDUCTORS TO BE LISTED AND MARKED SUNLIGHT RESISTANT 6. CONDUCTOR SIZE TO BE #1 FOR 125 AMP. BREAKER 7. RECALL WHEN READY |