Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T08CM01664
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/01/2008 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
07/28/2008 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* PROPER TAPS NOT INSTALLED |
|
07/25/2008 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* ALL CORRECTIONS MADE DATED 7/23/08 EXCEPT #3, #6, #8 OK FOR CEILING TILES OPEN OFFICE AREA MECHANICAL ONLY |
|
07/23/2008 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. FLEXES NOT CONNECTED 2. SEAL ALL JOINTS IN DUCT 3. CONNECT 3/8 CONDENSATE PIPING 4. PROVIDE HOSE CLAMPS ON RUBBER TUBING 5. IMPROPER RADIUS ON FLEX RUNS 6. PROVIDE PROPER BRANCH TAPS PER PLANS 7. FLEX CANNOT BE SUPPORTED BY OTHER TRADES 8. INSULATE ROUND DUCT |