Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T08CM01652
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/09/2008 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* OK FOR CEILING TILES |
|
10/02/2008 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. FIRE DAMPERS STILL NOT INSTALLED CORRECTLY. 2. THE BLADES IN THE DAMPERS MUST BE WITHIN THE OPENING IN WALL. 3. INSTALL YOUR GRID CEILING, FLEX AND DIFFUSERS THEN SCHEDULE ABOVE CEILING. |
|
09/30/2008 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* MECHANICAL SPECIFICATIONS (6) - DUCT SUPPORTS @ 4' MAX (9) - PROPERLY SUPPORT FLEX DUCT NO NYLON ON SITE (12) - VERIFY FLEX CONNECTORS AT UNITS MECHANICAL DETAILS (8) - REFERS TO SPEC. 12 ALSO, VERIFY INSULATION IN CURB PER DETAIL 8 (2) - SHEET METAL SADDLE AND HANGER STRAP (11) - ONLY SPIN-IN TAPS ALLOWED NO DOVE TAIL TAPS (DETAIL 2 ALSO REFERS TO THIS) (4) - FIRE DAMPER IN PLANE OF WALL, PROVIDE ACCESS DOOR FRAME OUT HOLES PER DETAIL VERIFY ALL DUCT JOINTS SEALED MAKE ALL CORRECTIONS PRIOR TO NEXT INSPECTION |