Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T08CM01641

Parcel: 136330030


Addresses:

9121 E 38TH ST

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/29/2008 ELECTRIC - FINAL Denied ARIN @ 940-6700 (CARL'S SERVICE)

EST LOAD CALC = 130 AMP
SERVICE RATED = 100 AMP

NEED TO UPGRADE SERVICE

NOTIFIED ARIN OF DENIAL, AND ASKED FOR CALL BACK
05/27/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED HEAT STRIPS MARKED ON UNIT
2) NEED LOAD CALCULATIONS FOR PANEL. APPEARS TO BE JUST 100 AMP TOTAL CAPACITY