Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/29/2008 | ELECTRIC - FINAL | Denied | ARIN @ 940-6700 (CARL'S SERVICE) EST LOAD CALC = 130 AMP SERVICE RATED = 100 AMP NEED TO UPGRADE SERVICE NOTIFIED ARIN OF DENIAL, AND ASKED FOR CALL BACK |
|
| 05/27/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED HEAT STRIPS MARKED ON UNIT 2) NEED LOAD CALCULATIONS FOR PANEL. APPEARS TO BE JUST 100 AMP TOTAL CAPACITY |