Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM01640
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/19/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* RECEIVED MONEY ORDER#0777327439 - $150.00 |
|
10/17/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* ROOF: 1. MAINTAIN WORKING CLEARANCES AC DISCONNECTING MEANS - 110.26 2. ISOLATE CONDUCTORS TO OVERCURRENT DEVICE 3. PROTECT SEALTITE FROM SHARP METAL EDGES INTERIOR: SUPPORT M/C & FLEX AS PER CODE |
|
10/16/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. GROUND ALL FIXTURES 2. BOXES TO BE ACCESSIBLE 3. DERATE CONDUCTORS PER 310.15 |
|
10/06/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. GROUND JUNCTION BOXES - 250.146 2. SHEETMETAL THREAD SCREWS NOT ALLOWED FOR GROUNDING - 250.8 3. VDV CABLING TO BE AS PER 725.6 & 24, 800.6 & 24, 300.11, 815, 820 4. NEED DISCONNECTING MEANS FOR SCREEN MOTOR 5. BOXES MORE THAN 1/8" AROUND 314.21 6. ATTACH FIXTURE TO GRID 410.16 7. ELECTRICAL SUPPORTING TO BE INDEPENDENT - 300.11 8. MAINTAIN WORKING CLEARANCES - 110.26 9. REVISED PANEL SCHEDULES PER 408.4 10. FILL UNUSED OPENINGS AND BOXES |