Permit: T08CM01640

Parcel: 10509550A


Addresses:

4841 N STONE AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/19/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
RECEIVED MONEY ORDER#0777327439 - $150.00
10/17/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
ROOF:
1. MAINTAIN WORKING CLEARANCES AC DISCONNECTING MEANS - 110.26
2. ISOLATE CONDUCTORS TO OVERCURRENT DEVICE
3. PROTECT SEALTITE FROM SHARP METAL EDGES

INTERIOR:
SUPPORT M/C & FLEX AS PER CODE
10/16/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. GROUND ALL FIXTURES
2. BOXES TO BE ACCESSIBLE
3. DERATE CONDUCTORS PER 310.15
10/06/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. GROUND JUNCTION BOXES - 250.146
2. SHEETMETAL THREAD SCREWS NOT ALLOWED FOR GROUNDING - 250.8
3. VDV CABLING TO BE AS PER 725.6 & 24, 800.6 & 24, 300.11, 815, 820
4. NEED DISCONNECTING MEANS FOR SCREEN MOTOR
5. BOXES MORE THAN 1/8" AROUND 314.21
6. ATTACH FIXTURE TO GRID 410.16
7. ELECTRICAL SUPPORTING TO BE INDEPENDENT - 300.11
8. MAINTAIN WORKING CLEARANCES - 110.26
9. REVISED PANEL SCHEDULES PER 408.4
10. FILL UNUSED OPENINGS AND BOXES