Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T08CM01629
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/02/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
10/01/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. REMOVE ALL FOIL TAPE FROM FURNACE & WATER HEATER VENTS 2. YOU ARE NOT REQUIRED TO SEAL THESE VENTS. 3. FOIL TAPE IS NOT APPROVED FOR VENT PIPING 4. NEED TO SEE ALL CONNECTIONS 5. PROVIDE MIN. 2" CLEARANCE FROM COMBUSTIBLE AROUND DRYER VENTS AND 1" AROUND FURNACE VENT. 6. PROVIDE INSULATION SHIELD AT FURNACE VENT 7. MARK UNIT DATA PLATE ON AC UNIT |
|
09/26/2008 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
09/24/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PRIOR CORRECTIONS NOT DONE, REFEE WILL APPLY IF WORK NOT COMPLETE PRIOR TO NEXT INSPECTION |
|