Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
02/06/2009 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
01/21/2009 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
12/30/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
12/29/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) PROVIDE HEAT SENSORS IN TYPE I EXHAUST DUCTS PER 507.2.1.1 2006 IMC.
2) PROVIDE AIR BALANCE REPORT
3) NEED CAPTURE AND CONTAMINENT TEST
4) SEAL BOTTOM OF SHAFTS
5) PROVIDE PROPER FITTINGS ON WATER HEATER DRAIN HOSE
12/26/2008 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) DOORS LOCKED
2) NOBODY ON SITE
08/19/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
SUSPENDED ROUGH DUCT
OK TO PROCEED
HOOD MUST BE MIN. 18" FROM WOOD FRAMED WALL