Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/06/2009 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 01/21/2009 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 12/30/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 12/29/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) PROVIDE HEAT SENSORS IN TYPE I EXHAUST DUCTS PER 507.2.1.1 2006 IMC. 2) PROVIDE AIR BALANCE REPORT 3) NEED CAPTURE AND CONTAMINENT TEST 4) SEAL BOTTOM OF SHAFTS 5) PROVIDE PROPER FITTINGS ON WATER HEATER DRAIN HOSE |
|
| 12/26/2008 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) DOORS LOCKED 2) NOBODY ON SITE |
|
| 08/19/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* SUSPENDED ROUGH DUCT OK TO PROCEED HOOD MUST BE MIN. 18" FROM WOOD FRAMED WALL |