Permit: T08CM01628

Parcel: 13615378B

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
01/20/2009 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
01/16/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
12/26/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSTALL SIESMIC WIRES ON TRACK LIGHT, 2 X 4 FIXTURES
2) ATTACH 2 X 4 FIXTURES TO CEILING GRID
3) CLOSE OPEN JUNCTION BOX IN CEILING/CLOSE OPEN KNOCKOUT
4) ALL KITCHEN RECEPTACLES TO BE GFI PROTECTED
5) NEED PANEL DIRECTORIES
6) MISSING EM LIGHTS
7) RECESSED FIXTURES INSTALLED ARE NOT PER PLAN AS SPECIFIED
8) SEAL RACEWAYS INTO COOLERS
9) INSTALL EQUIPMENT GROUNDS THRU METAL FLEX
10) CONNECT EQUIPMENT GROUNDS TO GUTTER OF SHUT DOWN SYSTEM
11) FINISH INSTALLING ALL EQUIPMENT
12) NEED TO CHECK ROOF AT NEXT INSPECTION