Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/20/2009 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 01/16/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 12/26/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL SIESMIC WIRES ON TRACK LIGHT, 2 X 4 FIXTURES 2) ATTACH 2 X 4 FIXTURES TO CEILING GRID 3) CLOSE OPEN JUNCTION BOX IN CEILING/CLOSE OPEN KNOCKOUT 4) ALL KITCHEN RECEPTACLES TO BE GFI PROTECTED 5) NEED PANEL DIRECTORIES 6) MISSING EM LIGHTS 7) RECESSED FIXTURES INSTALLED ARE NOT PER PLAN AS SPECIFIED 8) SEAL RACEWAYS INTO COOLERS 9) INSTALL EQUIPMENT GROUNDS THRU METAL FLEX 10) CONNECT EQUIPMENT GROUNDS TO GUTTER OF SHUT DOWN SYSTEM 11) FINISH INSTALLING ALL EQUIPMENT 12) NEED TO CHECK ROOF AT NEXT INSPECTION |