Permit: T08CM01623

Parcel: 11310288B


Addresses:

2455 N CAMPBELL AV

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
09/05/2008 ELECTRIC - INTERMEDIATE Approved
08/21/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CANCELED
08/20/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WIRING TO BOX

1. PANEL HEIGHT NOT OVER 6'7"
08/15/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. NEED TO SEE CONNECTIONS TO A BOX
2. NM CABLE DATED 12/13/2007
08/13/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
OK 1 - 1/2" EMT ABOVE CEILING - OLD SPACE

1. NEW WIRING NEEDS TO BE INSPECTED - OPEN AS DISCUSSED
2. #14 GAUGE WIRE (NM CABLE) TOO SMALL