Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/09/2008 | PLUMBING - ROUGH, SOIL | Approved | ||
| 07/25/2008 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* DWV W/TEST OK 904.1 REQUIRES THAT EACH CONN TO A SEWER BE VENTED BY VENT PIPES W/AN AGGREGATE CROSS-SECTIONAL AREA EQUAL TO THE AREA OF THE REQUIRED BUILDING SEWER WHICH IS 3" IN THIS CASE. PROVIDE A 3" VENT AT BW VALVE LOCATION. YOU MAY COVER AFTER CORRECTING SITE SEWER TO COMBO LOCATED 12' ON STEM |
|
| 07/23/2008 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999* MAX. TRAP ARM DISTANCE IS 5' 2" VENT SPECIFIED FOR FLOOR DRAIN UNCOVER FITTINGS, BELL UNDER FITTINGS TOP OFF WATER TEST CORRECT SLOPE AT WC PLAN DOES NOT SPECIFY BACKWATER VALVE IT DOES APPEAR TO NEED ONE REVISE SITE UTILITY PLAN TO SHOW AND INSTALL A VENT DOWNSTREAM OF BW VALVE PER UPC 904-1 PLAN DOES NOT SHOW BRANCH ON SEWER USE 03055 FOR SEWER INSP. INSTALL TRACER WIRE |