Permit: T08CM01596

Parcel: 132160480


Addresses:

1530 E BENSON HY


Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T08CM01596

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
12/09/2008 PLUMBING - ROUGH, SOIL Approved
07/25/2008 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
DWV W/TEST OK

904.1 REQUIRES THAT EACH CONN TO A SEWER BE VENTED BY VENT PIPES W/AN AGGREGATE CROSS-SECTIONAL AREA EQUAL TO THE AREA OF THE REQUIRED BUILDING SEWER WHICH IS 3" IN THIS CASE. PROVIDE A 3" VENT AT BW VALVE LOCATION. YOU MAY COVER AFTER CORRECTING SITE SEWER TO COMBO LOCATED 12' ON STEM
07/23/2008 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
MAX. TRAP ARM DISTANCE IS 5'
2" VENT SPECIFIED FOR FLOOR DRAIN
UNCOVER FITTINGS, BELL UNDER FITTINGS
TOP OFF WATER TEST
CORRECT SLOPE AT WC
PLAN DOES NOT SPECIFY BACKWATER VALVE
IT DOES APPEAR TO NEED ONE
REVISE SITE UTILITY PLAN TO SHOW AND INSTALL A VENT DOWNSTREAM OF BW VALVE PER UPC 904-1

PLAN DOES NOT SHOW BRANCH ON SEWER
USE 03055 FOR SEWER INSP.
INSTALL TRACER WIRE