Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/29/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/26/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection OK TO CLEAR SUBJECT TO BOND POSTING POST BOND FOR TEMP POWER FOR TESTING |
|
| 11/25/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. INSTALL BUSHINGS ON 4" CONDUIT ENDS AT CT CAB 2. PLANS CALL FOR COPPER FEEDERS 3. HAVE ELECTRICAL CONTR. OPEN ALL ELEC. EQUIP. FOR INSEPCTION 4. PANEL "A" TO COMPLY WITH PLAN-65K AIC |