Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T08CM01596

Parcel: 132160480


Addresses:

1530 E BENSON HY


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM01596

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/29/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/26/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection
OK TO CLEAR SUBJECT TO BOND POSTING
POST BOND FOR TEMP POWER FOR TESTING
11/25/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. INSTALL BUSHINGS ON 4" CONDUIT ENDS AT CT CAB
2. PLANS CALL FOR COPPER FEEDERS
3. HAVE ELECTRICAL CONTR. OPEN ALL ELEC. EQUIP. FOR INSEPCTION
4. PANEL "A" TO COMPLY WITH PLAN-65K AIC