Permit: T08CM01594

Parcel: 10511061R

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM01594

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/03/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
LV POWER SUPPLIES ARE BEING REMOVED
08/28/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. CARDS DISPLAY OUTLET BOX NOT GROUNDED & CORD NOT ALLOWED PER 400.7 & 8
2. PANEL DIRECTORIES TO BE AS PER 408.4 - NO ABBREVIATIONS
3. PANEL (480V) FILLERS TO BE FOR PANEL OR SAME THICKNESS METAL
4. BOXES MORE THAN 1/4" FROM BOX TO SURFACE - 314.20
5. SUPPORT WIRES NEEDED ALL FIXTURES
6. EM LIGHT NOT WORKING
7. TIME CLOCK AND CONTACTOR (MISSING) NOT AS PER PLANS
8. PLEASE VERIFY LISTING FOR LOW VOLTAGE POWER SUPPLIES AND WIRE FOR RETURN AIR