Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T08CM01575
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/17/2008 | FRAMING | Approved | IVRS - Inspection :* | |
07/16/2008 | FRAMING | Partial Approval | IVRS - Inspection :* 1) OK TO HANG CEILING 2) COMPLY AND CHECK SHEARWALL BETWEEN KITCHEN AND DINING ROOM |
|
07/15/2008 | FRAMING | Partial Approval | IVRS - Inspection :* 1) SEE LIST 1-5 BELOW NEED SHEAR TRANSFER AT REAR INTERIOR 2) WILL CHECK ON PLATE NAILS |
|
07/11/2008 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ABOVE DOOR TO HOUSE FROM GARAGE NAIL END ROOF NAILER TO WALL 2. ADD STUD AT WASHER BOX SHEAR WALL 3. TUB SURROUND BACKING & SHOWER 4. WHAT ARE YOU USING FOR BOTTOM PLATE NAILING TO CONCRETE? 5. BLK. ALL MECH DUCTS 6. AT ENTRY TO MASTER BED. WALL NOT TIED TO TRUSSES 7. PREVIOUS INSPECTION REPORTS NOT ON SITE HAVE ALL TRUSSES, TRUSS REPAIRS BEEN APPROVED? 8. INTERIOR SHEAR WALL TRANSFERS NOT DONE |