Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T08CM01550
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/15/2008 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* PETITION OF APPEAL FOR 2006 IPC ON SITE SHOWERS OK |
|
09/23/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - 2ND LEVEL SHOWER VALVES & STALLS EXCEPT HANDICAP AND WATER TEST ON ALL DRAINS. - 2ND LEVEL DRAINAGE OK - 1ST LEVEL SHOWERS OK 1" CW, PIPED IN CPVC TO (3) LOCATIONS AND CONTINUOUS TO DEIONIZER WITH JUMPER FOR 1" CPVC FUTURE FOR TEST ON THIS PIPING OK 1" CW MAY REQUIRE BACKFLOW PROTECTION AT EACH PIECE OF EQUIPMENT AND DEIONIZER WHEN SYSTEM IS COMPLETED TO EQUIPMENT. NOTE: PLEASE PROVIDE YOUR PETITION OF APPEAL FORM ON SITE FOR INTERNATIONAL PLUMBING CODE USE ON THIS PROJECT |
|
09/08/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* P-2 WASTE & VENT 1ST & 2ND FLOORS - TEST OK PROVIDE SLOPE ON 2ND FLOOR WASTE WATER PIPING OK TO INSULATE SHWR VALVES NOT YET INSTALLED |
|
08/27/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* WATER TEST SOUTHEAST 3" RD & OFRD RE-ROUTE OK DWV 1ST LEVEL ONLY TO TIE-INS TO EXISTING |