Permit: T08CM01550

Parcel: 12810078B


Addresses:

5411 E WILLIAMS BL


Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T08CM01550

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
04/08/2009 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
03/06/2009 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
11/12/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. OK CEILINGS 1ST FLOOR
2. OK CEILING 2ND FLOOR LAB
11/09/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
11/05/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. OK CEILINGS RMS. 134, 126-131, 133

NEED TO CHARGE BARKER MORRISSEY $150.00
FOR AFTER HRS. INSPECTION
11/04/2008 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
CANCELED BY CONTRACTOR
10/31/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
2ND FLOOR CEILINGS:
OK CARE HALLWAYS AND OFFICES IN CARE AREA
EXCEPT LAB 2ND FLOOR

NEED TO CHARGE BARKER MORRISSEY
FOR $150 AFTER HRS. INSP. FROM APA ACCOUNT
10/24/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK CEILINGS 1ST FLOOR EAST OF CORRIDOR
10/23/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROPERLY SUPPORT/SECURE WIRES
2. CLOSE ALL OPEN JUNCTION BOXES
3. SEAL OPEN KNOCK OUTS
4. INSTALL SEISMIC WIRES ON ALL FIXTURES
10/22/2008 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
DO NOT SCHEDULE INSPECTIONS UNTIL ELECTRICAL CONTRACTOR IS READY
10/14/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK CEILINGS WEST SIDE OF FLOOR
RECALL FOR CORE AREAS
10/09/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) 2ND FLOOR EAST: SUPPORT VDV CABELING 725.24, 800.24, 760.24 & 300.11
3) OK LIGHTS M/C CABLE AND CONDUITS