Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T08CM01537
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/26/2009 | PLUMBING - FINAL | Approved | ROASTER APPROVED THROUGH FIELD EVALUATION SEALED BY P.E. | |
12/23/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* PROVIDE LISTING FOR ROASTER |
|
12/16/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. CALL IN ALL PLUMBING INSPECTIONS ON YOUR PERMIT CARD FOR APPROVAL 2. PROVIDE TEST ON GAS SYSTEM IN ENTIRETY 3. PROVIDE MINIMUM 1" AIR GAP ON ALL INDIRECT DRAINS 4. PROVIDE BACKFLOW CERTIFICATIONS ON ALL DEVICES 5. PROVIDE BACTERIA REPORT FOR POTABLE WATER 6. READ ALL NOTES AND INSTALL ACCORDINGLY 7. WATER HEATER EXPANSION TANK REQUIRES SUPPORT AND SECURE 8. ALL FIXTURES TO BE WATER TIGHT 9. HAVE LADDER AVAILABLE FOR WATER HEATER INSPECTION 10. WATER HEATER CANNOT BE SOLE CONTROL OF HOT WATER TEMPERATURE - NOT TO EXCEED 110 DEG. AT PUBLIC USE LAV 11. ROASTER REQUIRES A LISTING PLATE LIST MAY NOT BE COMPLETE |