Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T08CM01537
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/23/2008 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
08/28/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* ABV CEILING OK WILL NOT ACCEPT VENT 90 ON URINAL TRAP ARM |
|
08/19/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* GAS TEST DOWN TO 4 PSI CHECK (SOAP TEST) OK TO COVER IF HOLDING FOR GAS CLEARANCE; IDENTIFY AND TEST SYSTEM AND CORRECT ANY DAMAGED PIPE SUPPORTS. NEW RTU REQUIRES A SEDIMENT TRAP ON GAS SUPPLY AND PROPER CONDENSATE. HAVE RTU INSPECTED BY MECHANICAL INSPECTOR. WASTE OUTLET FOR URINAL WILL NOT WORK PROVIDE URINAL CUT SHEET AND CORRECT INSTALLATION |
|
08/15/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. T 6-5 REQUIRES 3/4" WATER FOR A URINAL FLUSHOMETER 2. ALSO, URINAL OUTLET SHALL BE THE SAME SIZE AS THE DRAIN ARM 3. DWV TEST THRU ROOF OK, RETEST IF CHANGES ARE MADE ABOVE CEILING 4. NOTE #4 REQUIRES HANGERS NOT CLAMPS. SUSPEND PIPING FROM STRUCTURE NOT TO IT 5. ABS REQUIRES SUPPORT AT EACH BRANCH CONN., EACH END AND NOT MORE THAN 4' OC 6. BACKING FOR MS FAUCET 7. 3/4 GAS PIPE IN WALL W/9.5PSI OK 8. PROVIDE 10 PSI TEST AND ACCESS TO ROOF |