Permit: T08CM01537

Parcel: 12810082B

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM01537

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/26/2009 ELECTRIC - FINAL Approved ROASTER APPROVED THROUGH FIELD EVALUATION SEALED BY P.E.
12/23/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. COFFEE ROASTER APPEARS TO BE UNLISTED. CANNOT LOCATE LISTING LABEL OR NAMEPLATE DATA. MANUFACTURE CANNOT INSTALL LISTING LABEL IN FIELD UNLESS LISTING AGENCY IS ONSITE. MAY NEED TO HAVE FIELD EVALUATION DONE BY NATIONALLY RECOGNIZED TESTING LAB. IF LISTING LABEL IS INSTALLED IN FIELD WITHOUT LISTING AGENCY ON SITE A FIELD REPORT WILL BE FILED WITH TESTING LAB.
2. NEED BOX EXTENSIONS ON RECEPTACLES IN WOOD PANELING.
12/16/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. COFFEE ROASTER APPEARS TO BE UNLISTED EQUIPMENT CANNOT LOCATE LABEL OR NAME PLATE DATA
2. NEED TO WIRE WATER HEATER
3. RECEPTACLES WITH NO POWER. INSTALL ALL DEVICES.
4. NOT ALL LIGHTS WORKING
5. NEED UPDATED ELECTRIC PANEL DIRECTORY
6. HAVE 48' OF TRACK LIGHTING CALCULATED LOAD IS 3800 WATTS PER NEC 220.43 (B) NEED ADDITIONAL CIRCUIT
ALSO, TRACK LIGHTING NOT INSTALLED PER PLAN.
7. NEED ROOFTOP GFI SERVICE RECEPT. SEE PLANS.
8. PROPERLY GROUND A/C UNIT
9. IDENTIFY EQUIPMENT GROUND TO A/C UNIT
ALONG ENTIRE LENGTH
10. HAVE PANEL OPEN FOR INSPECTION