Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM01537
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/26/2009 | ELECTRIC - FINAL | Approved | ROASTER APPROVED THROUGH FIELD EVALUATION SEALED BY P.E. | |
12/23/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. COFFEE ROASTER APPEARS TO BE UNLISTED. CANNOT LOCATE LISTING LABEL OR NAMEPLATE DATA. MANUFACTURE CANNOT INSTALL LISTING LABEL IN FIELD UNLESS LISTING AGENCY IS ONSITE. MAY NEED TO HAVE FIELD EVALUATION DONE BY NATIONALLY RECOGNIZED TESTING LAB. IF LISTING LABEL IS INSTALLED IN FIELD WITHOUT LISTING AGENCY ON SITE A FIELD REPORT WILL BE FILED WITH TESTING LAB. 2. NEED BOX EXTENSIONS ON RECEPTACLES IN WOOD PANELING. |
|
12/16/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. COFFEE ROASTER APPEARS TO BE UNLISTED EQUIPMENT CANNOT LOCATE LABEL OR NAME PLATE DATA 2. NEED TO WIRE WATER HEATER 3. RECEPTACLES WITH NO POWER. INSTALL ALL DEVICES. 4. NOT ALL LIGHTS WORKING 5. NEED UPDATED ELECTRIC PANEL DIRECTORY 6. HAVE 48' OF TRACK LIGHTING CALCULATED LOAD IS 3800 WATTS PER NEC 220.43 (B) NEED ADDITIONAL CIRCUIT ALSO, TRACK LIGHTING NOT INSTALLED PER PLAN. 7. NEED ROOFTOP GFI SERVICE RECEPT. SEE PLANS. 8. PROPERLY GROUND A/C UNIT 9. IDENTIFY EQUIPMENT GROUND TO A/C UNIT ALONG ENTIRE LENGTH 10. HAVE PANEL OPEN FOR INSPECTION |