Permit: T08CM01528

Parcel: 133502830

Inspection Status: Approved

Inspection History: EXCAVATION/LAYOUT REBAR & ZON

Permit Number - T08CM01528

Inspection Description - EXCAVATION/LAYOUT REBAR & ZON

Inspection Status - Approved

Date Description Inspector Results Comments
06/12/2008 EXCAVATION/LAYOUT REBAR & ZON Approved IVRS - Inspection :*
06/11/2008 EXCAVATION/LAYOUT REBAR & ZON Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. EXISTING FOOTINGS NOT TO DEPTH OF REQUIRED FOOTINGS. EXCAVATE UNDER THEM OR REMOVE THEM
2. NEED CONTINUOUS REBAR TOP AND BOTTOM WITH MINIMUM 24" OVERLAP
3. HAVE REBAR MINIMUM 3" FROM SOIL
4. TAP REBAR CAN RUN OVER EXISTING FOOTINGS
06/10/2008 EXCAVATION/LAYOUT REBAR & ZON Not ready for Inspection IVRS - Inspection :*
1) CANCELLED PER SUPER