Inspection History Details
Inspection Status: Approved
Inspection History: EXCAVATION/LAYOUT REBAR & ZON
Permit Number - T08CM01528
Inspection Description - EXCAVATION/LAYOUT REBAR & ZON
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/12/2008 | EXCAVATION/LAYOUT REBAR & ZON | Approved | IVRS - Inspection :* | |
06/11/2008 | EXCAVATION/LAYOUT REBAR & ZON | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. EXISTING FOOTINGS NOT TO DEPTH OF REQUIRED FOOTINGS. EXCAVATE UNDER THEM OR REMOVE THEM 2. NEED CONTINUOUS REBAR TOP AND BOTTOM WITH MINIMUM 24" OVERLAP 3. HAVE REBAR MINIMUM 3" FROM SOIL 4. TAP REBAR CAN RUN OVER EXISTING FOOTINGS |
|
06/10/2008 | EXCAVATION/LAYOUT REBAR & ZON | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED PER SUPER |