Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/22/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/18/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE LADDER TO INSPECT DROP CEILING AREAS 2. NEED DISCONNECTING MEANS FOR INSTANT HOT SEE PLANS AND NEC 422 3. PANEL SCHEDULES NOT PER PLAN 4. DO NOT SEE WIRING FOR OFFICE FURNITURE ON PLANS WIRING OF OFFICE FURNITURE TO BE PER NEC 605.6 & 605.7 5. 2X4 LIGHT FIXTURES TO BE ATTACHED TO CEILING GRID |