Permit: T08CM01507

Parcel: 131010520


Addresses:

4780 E 22ND ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/22/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/18/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PVC TO BE MIN. 24" BELOW GRADE TO TOP OF RACEWAY
2. NEED TO INSTALL 2 GROUND RODS
3. GROUND RODS TO BE DRIVEN
4. INSTALL CLAMP LISTED FOR USE ON GROUND RODS AND LISTED FOR DIRECT BURY
5. NEED SCHEDULE 80 PVC WHERE EXPOSED
6. BONDING JUMPER FROM XFMR TO DISCONNECT TO BE #2
7. RECALL WHEN READY