Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/22/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/18/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PVC TO BE MIN. 24" BELOW GRADE TO TOP OF RACEWAY 2. NEED TO INSTALL 2 GROUND RODS 3. GROUND RODS TO BE DRIVEN 4. INSTALL CLAMP LISTED FOR USE ON GROUND RODS AND LISTED FOR DIRECT BURY 5. NEED SCHEDULE 80 PVC WHERE EXPOSED 6. BONDING JUMPER FROM XFMR TO DISCONNECT TO BE #2 7. RECALL WHEN READY |