Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/31/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* WILDAN APPROVED CHANGES |
|
| 10/29/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. FILL UNUSED OPENINGS IN BOXES - NOT EMPTY FITTINGS 2. BREAKER TO BE LISTED FOR USE BY MANUFACTURE 3. BOXES MORE THAN 1/4" -- 314.20 OR MORE THAN 1/8" AROUND -- 314.21 4. SUPPORT WIRE NEEDED FOR CANS 5. CLEAN EXCESS DIRT & FOREIGN MATERIAL FROM PANELS 6. SEAL UNUSED CONDUIT OPENINGS 7. LIGHTING PLANS NOT REVISED AND RESTAMPED ROOF: 1. TIGHTEN LOOSE FITTINGS *PLEASE RETIGHTEN ALUMINUM TERMINATIONS |