Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
Permit Number - T08CM01493
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/27/2008 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* | |
06/06/2008 | ELECTRIC - CABLE DROP | Not ready for Inspection | IVRS - Inspection :* 1. NEED TO HAVE CT CABINET OPEN 2. FINISH INSTALLING SECONDARY CONDUCTORS 3. INSTALL FUSES AND BONDING JUMPERS 4. EQUIPMENT GROUNDS LEAVING 800 AMP DISCONNECT NOT SIZED PROPERLY - NEC 250.122 5. OK UNDERGROUND TO TEP XFMR FROM CT CABINET INSTALL WARNING RIBBON PER NEC 300.5 6. OK WALLS |