Permit: T08CM01490

Parcel: 12501022A


Addresses:

2555 E 1ST ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
08/15/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
GAS PIPING INSTALLED OK
PRESSURE TEST OK
PLUMBING FINAL OK
08/12/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
PER 301.1.2 2006 UPC
EACH SECTION OF PIPE SHALL CARRY THE LISTING FOR THAT PIPE I.E A-53 OR A-53A
IF GAS PIPING DOES NOT CARRY THE A53 DESIGNATION, IT IS DEEMED UNACCEPTABLE FOR NATURAL GAS. ONLY PIPING WITH THE A53 DESIGNATION WILL BE ACCEPTED. CONTINUED "NOT READY" WILL RESULT IN A REINSPECTION FEE.
08/11/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
THIS INSPECTION FOR CLOSET FLANGES
RESTROOMS 108 & 110 OK
08/04/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. RESTROOMS AVAILABLE IN PHASE ONE
2. INSULATE HOT WATER PIPING AT WATER HEATER
3. PHASE TWO RESTROOMS NOT COMPLETE
REQUIRE CLEAN BACTERIA REPORT