Permit: T08CM01481

Parcel: 128010190

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T08CM01481

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/19/2009 MECHANICAL - FINAL Approved IVRS - Inspection :*
06/18/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) COMPLETE AIR BALANCE ON EF
2) PROVIDE DUCT SMOKE DETECTOR TEST
06/16/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
*PROVIDE DOCUMENTATION ON DUCT DETECTOR TEST

1. PROVIDE INSULATION SHIELD ON UNIT HEATER
2. FLASH RTU DUCT AT PENETRATIONS
3. PROVIDE APPROVED COVERS FOR DUCT SMOKE DETECTORS
4. PROVIDE PROPER FUSES AT RTU's
5. AIR BALANCE NOT COMPLETE
06/10/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. FINISH AIR BALANCE
2. OK FOR CEILING TILES
3. PAINT EXPOSED PVC W/LATEX PAINT
4. INSULATION ON EXPOSED DUCT ONLY R4.3 PROVIDE R8
5. DUCT SMOKE DETECTORS NOT PROPERLY MOUNTED
6. PROVIDE WEATHERPROOF COVERS
7. INSULATION ON EXPOSED DUCT NOT INSTALLED CORRECTLY
8. FINISH INSULATING TOP OF DIFFUSERS