Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM01481
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/18/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
06/16/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. STRAP METAL FLEX WITHIN 12" OF CONNECTIONS 2. USE ALL MOUNTING HARDWARE FOR RECEPTS. IN INDUSTRIAL COVERS 3. STRAP RACEWAYS TO DISPLAY SHELVES 4. OPEN DISPLAY SHELVES TO SEE WIRING 5. INSTALL END CAPS ON DISPLAY LIGHTING AND TERMINATE MC CABLE INTO PROPER KNOCKOUT 6. STRAP MC CABLE WITHIN 12" OF CONNECTIONS 7. SEAL OPEN KNOCKOUTS 8. TIGHTEN LOCKNUTS @ PANELS 9. INSTALL ARC FLASH WARNING LABELS ON ALL PANELS 10. LABEL ALL BREAKERS 11. ONE GROUND PER TERMINAL @ DISCONNECT 12. ROOFTOP UNITS OVERFUSED 13. INSTALL PROPER COLORED WIRE 14. TIGHTEN ALL SEAL TIGHT FITTINGS 15. STRAP SEAL TIGHT WITHIN 12" OF CONNECTIONS 16. BRANCH CIRCUIT CONDUCTORS TO EXHAUST FAN TO TERMINATE IN JUNCTION BOX 17. ONE EXIT NOT WORKING WHEN TESTED |