Permit: T08CM01481

Parcel: 128010190

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM01481

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/18/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/16/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. STRAP METAL FLEX WITHIN 12" OF CONNECTIONS
2. USE ALL MOUNTING HARDWARE FOR RECEPTS. IN INDUSTRIAL COVERS
3. STRAP RACEWAYS TO DISPLAY SHELVES
4. OPEN DISPLAY SHELVES TO SEE WIRING
5. INSTALL END CAPS ON DISPLAY LIGHTING AND TERMINATE MC CABLE INTO PROPER KNOCKOUT
6. STRAP MC CABLE WITHIN 12" OF CONNECTIONS
7. SEAL OPEN KNOCKOUTS
8. TIGHTEN LOCKNUTS @ PANELS
9. INSTALL ARC FLASH WARNING LABELS ON ALL PANELS
10. LABEL ALL BREAKERS
11. ONE GROUND PER TERMINAL @ DISCONNECT
12. ROOFTOP UNITS OVERFUSED
13. INSTALL PROPER COLORED WIRE
14. TIGHTEN ALL SEAL TIGHT FITTINGS
15. STRAP SEAL TIGHT WITHIN 12" OF CONNECTIONS
16. BRANCH CIRCUIT CONDUCTORS TO EXHAUST FAN TO TERMINATE IN JUNCTION BOX
17. ONE EXIT NOT WORKING WHEN TESTED