Permit: T08CM01476

Parcel: 141014880

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM01476

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/29/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/20/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. DO NOT HAVE PROPER WORKING CLEARANCE IN FRONT OF EQUIPMENT BECAUSE OF GAS METER
2. ELECTRICAL EQUIPMENT TO BE 3' MIN. AWAY FROM REGULATOR VENT ON GAS METER
3. PROPERLY TERMINATE GROUNDS IN DISCONNECT. INSTALL GROUND BAR MADE FOR DISCONNECT. CANNOT USE TECH SCREW FOR GROUND CONNECTION. LUG NOT RATED
FOR 2-WIRE TERMINATION
4. DISCONNECT TOP OPEN BOTH (+) & (-) CONDUCTORS
5. INSTALL WARNING ABOUT BACK FED BREAKERS
6. CANNOT INSTALL SOLID WIRE LARGER THAN #10 IN RACEWAYS
7. PROPERLY TERMINATE GROUNDS IN JUNCTION BOXES ON ROOF LUGS NOT LISTED FOR MULTIPLE WIRE TERMINATIONS