Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/29/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/20/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. DO NOT HAVE PROPER WORKING CLEARANCE IN FRONT OF EQUIPMENT BECAUSE OF GAS METER 2. ELECTRICAL EQUIPMENT TO BE 3' MIN. AWAY FROM REGULATOR VENT ON GAS METER 3. PROPERLY TERMINATE GROUNDS IN DISCONNECT. INSTALL GROUND BAR MADE FOR DISCONNECT. CANNOT USE TECH SCREW FOR GROUND CONNECTION. LUG NOT RATED FOR 2-WIRE TERMINATION 4. DISCONNECT TOP OPEN BOTH (+) & (-) CONDUCTORS 5. INSTALL WARNING ABOUT BACK FED BREAKERS 6. CANNOT INSTALL SOLID WIRE LARGER THAN #10 IN RACEWAYS 7. PROPERLY TERMINATE GROUNDS IN JUNCTION BOXES ON ROOF LUGS NOT LISTED FOR MULTIPLE WIRE TERMINATIONS |