Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T08CM01471
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/01/2009 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
04/29/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. REPAIR INSULATION WHERE CUT OR TORN ON DUCT 2. PROVIDE A SUBSTANTIAL COLLAR ON ALL REGISTERS TO ATTACH FLEX 1 1/2" NOT ENOUGH. MIN. 4" 3. INSULATE RETURN BOOT BOXES 4. PROVIDE SEISMIC RESTRAINT WIRES ON ALL REGISTERS IN T-BAR 5. PROVIDE FLEX SUPPORT AS NEEDED TO AVOID SAGGINS |
|
04/27/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
04/24/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE FINISH CONNECTING DIFFUSERS AND FLEX DUCTS |
|
04/09/2009 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE SCOOPS IN ALL ROUND BRANCH TAPS PER PLANS 2. SEAL ALL BRANCH TAPS WITH SEALANT PER PLANS 3. SUPPLY AND RETURN DUCT TO BE LINED WITH 1" LINER A MIN. OF 15' FROM UNIT PER PLANS |