Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T08CM01471

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
05/01/2009 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
04/29/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. REPAIR INSULATION WHERE CUT OR TORN ON DUCT
2. PROVIDE A SUBSTANTIAL COLLAR ON ALL REGISTERS TO ATTACH FLEX 1 1/2" NOT ENOUGH. MIN. 4"
3. INSULATE RETURN BOOT BOXES
4. PROVIDE SEISMIC RESTRAINT WIRES ON ALL REGISTERS
IN T-BAR
5. PROVIDE FLEX SUPPORT AS NEEDED TO AVOID SAGGINS
04/27/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
04/24/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
CORRECTIONS HAVE BEEN MADE
FINISH CONNECTING DIFFUSERS AND FLEX DUCTS
04/09/2009 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE SCOOPS IN ALL ROUND BRANCH TAPS PER PLANS
2. SEAL ALL BRANCH TAPS WITH SEALANT PER PLANS
3. SUPPLY AND RETURN DUCT TO BE LINED WITH 1" LINER
A MIN. OF 15' FROM UNIT PER PLANS