Permit: T08CM01444

Parcel: 10511061R

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/11/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/08/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. CANNOT CUT OFF "UL" LISTED CABINET CORD CAP
2. TIGHTEN LOOSE FITTINGS
3. STOCK ROOM EXIT LIGHT TO BE ON CIRCUIT
AREA SERVED 700.12
4. BOXES MORE THAN 1/4" FROM BOX TO SURFACE - 314.20
5. CLEAN EXCESS DIRT FROM BOTTOM OF PANEL
6. HAVE ELECTRICIAN OPEN TRANSFORMER TO INSPECT CONNECTIONS AND CONTACTOR BOX