Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/11/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/08/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. CANNOT CUT OFF "UL" LISTED CABINET CORD CAP 2. TIGHTEN LOOSE FITTINGS 3. STOCK ROOM EXIT LIGHT TO BE ON CIRCUIT AREA SERVED 700.12 4. BOXES MORE THAN 1/4" FROM BOX TO SURFACE - 314.20 5. CLEAN EXCESS DIRT FROM BOTTOM OF PANEL 6. HAVE ELECTRICIAN OPEN TRANSFORMER TO INSPECT CONNECTIONS AND CONTACTOR BOX |