Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T08CM01443
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/02/2008 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* OK FOR SHEETROCK |
|
09/30/2008 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* FINISH FIRE BLOCKING COMBUSTIBLES IN SOFFIT |
|
08/19/2008 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
08/13/2008 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. YOU CANNOT PULL RETURN AIR FROM A BATHROOM 2. PROVIDE A TRAP ON CONDENSATE DRAIN LINE 3. NO COMBUSTIBLES - PLASTIC, WOOD, ETC. IN A RETURN AIR PLENUM 4. PROVIDE APPROVED PLANS 5. RECOMMEND RELOCATING FAN COIL OUT TO HALLWAY |